PDF p. 1096 · 22-41
If accidental system discharge occurs, ventilate work area before resuming service.
R-134a service equipment or vehicle air conditioning systems should not be pressure tested or leak tested with compressed air.
Additional health and safety information may be obtained from the refrigerant and lubrication manufacturers.
NOTE: Use only a gauge set for refrigerant HFC-134a (R-134a).
- Use only a gauge set for refrigerant HFC-134a (R-134a).
- Us a vacuum pump adapter which is equipped with a check valve to prevent backflow of the vacuum pump oil.
- 1.Close the evacuation valve (two valve gauge; evacuation stop valve).
- 2.Open the cans.
- 3.
Open the high pressure valve to charge the system to about 98 kPa (1.0 kgf/cm2, 14 psi), then close it.
NOTE: Close the low pressure valve.
- 4.
Check the system for leaks using a leak detector for refrigerant R-134a.
NOTE: Particularly check for leaks around the compressor, condenser and receiver/dryer.
- 5.If you find any leaks, tighten the joint nuts and bolts to the specified torque.
- 6.Recheck the system for leaks using the leak detector.
- 7.If you find leaks that require the system to be opened (to repair or replace hoses, fittings etc), release any charge in the system.
- 8.After checking and repairing leaks, the system must be evacuated (System Evacuation (See Page 22-39).
THREE VALVE GAUGE TWO VALVE GAUGE

- 1. LOW PRESSURE VALVE
- 2. EVACUATION VALVE
- 3. HIGH PRESSURE VALVE
- 4. VACUUM PUMP
- 5. 16 mm
- 6. HIGH PRESSURE QUICK JOINT
- 7. LOW PRESSURE QUICK JOINT
- 8. 13 mm
- 9. CHECK VALVE
- 10. LOW PRESSURE VALVE
- 11. HIGH PRESSURE VALVE
- 12. EVACUATION STOP VALVE
- 13. VACUUM PUMP
- 14. 16 mm
- 15. HIGH PRESSURE QUICK JOINT
- 16. LOW PRESSURE QUICK JOINT
- 17. 13 mm
- 18. CHECK VALVE