Workshop manual

A/C System Service

Evacuation

Shop Manual 1999 · source: HRV_Workshop_Manual.pdf, PDF page 1094 (manual page 22-39)

PDF p. 1094 · 22-39

NOTE:

  • Use only a gauge set for refrigerant HFC-134a (R-134a).
  • Us a vacuum pump adapter which is equipped with a check valve to prevent backflow of the vacuum pump oil.

If accidental system discharge occurs, ventilate work area before resuming service. Additional health and safety information may be obtained from the refrigerant and lubricant manufacturer.

  1. 1.
    When an A/C System has been opened to the atmosphere, such as during installation or repair, it must be evacuated using a R-134a refrigerant vacuum pump. (If the system has been open for several days the receiver/dryer should be replaced.)
  1. 2.
    Connect the R-134a gauge set, pump and refrigerant containers (cans of R-134a) as shown.
  2. 3.
    Start the pump, then open both pressure valves and the evacuation valve (two valve gauge; evacuation stop valve). Run the pump for about 15 minutes.
  3. 4.

    Close both pressure valves and the evacuating valve (two valve gauge; evacuation stop valve) and stop the pump. The low pressure gauge should indicate above 93.3 kPa (700 mmHg, 27.6 in/Hg) and remain steady with the valves closed.

    NOTE: If the low pressure does not reach more than 93.3 kPa (700 mmHg, 27.6 in/Hg) in 15 minutes, there is probably a leak in the system. Check for leaks and repair (see Leak Test).

  4. 5.
    If there are no leaks, open the valves and continue pumping for at least another 15 minutes. The close both valves and stop the pump.

THREE VALVE GAUGE TWO VALVE GAUGE

Illustration: LOW PRESSURE VALVE; EVACUATION VALVE; HIGH PRESSURE VALVE; VACUUM PUMP; 16 mm; LOW PRESSURE QUICK JOINT; 13 mm; HIGH PRESSURE QUICK JOINT; CHECK VALVE; LOW PRESSURE VALVE; HIGH PRESSURE VALVE; EVACUATION STOP VALVE; VACUUM PUMP; 16 mm; LOW PRESSURE QUICK JOINT; 13 mm; HIGH PRESSURE QUICK JOINT; CHECK VALVE
  1. 1. LOW PRESSURE VALVE
  2. 2. EVACUATION VALVE
  3. 3. HIGH PRESSURE VALVE
  4. 4. VACUUM PUMP
  5. 5. 16 mm
  6. 6. LOW PRESSURE QUICK JOINT
  7. 7. 13 mm
  8. 8. HIGH PRESSURE QUICK JOINT
  9. 9. CHECK VALVE
  10. 10. LOW PRESSURE VALVE
  11. 11. HIGH PRESSURE VALVE
  12. 12. EVACUATION STOP VALVE
  13. 13. VACUUM PUMP
  14. 14. 16 mm
  15. 15. LOW PRESSURE QUICK JOINT
  16. 16. 13 mm
  17. 17. HIGH PRESSURE QUICK JOINT
  18. 18. CHECK VALVE