PDF p. 1100 · 22-44
NOTE: For performance test (See Page 22-42)
| Test results | Related symptoms | Probable cause | Remedy | ||
|---|---|---|---|---|---|
| Discharge (high) | After stopping compressor, | Air in system | Discharge, evacuate, and recharge with | ||
| pressure | pressure drops to about | specified amount. | |||
| abnormally high | 200 kPa (2.0 kgf/cm2, 28 | Evacuation: (See Page 22-39) | |||
| psi) quickly, and then falls | Charging: (See Page 22-40) | ||||
| gradually | |||||
| Discharge (high) | No bubbles in sight glass | Excessive refrigerant in | Discharge, evacuate and recharge with | ||
| pressure | when condenser is cooled | system | specified amount. | ||
| abnormally high | by water. | ||||
| Discharge (high) | Reduced or no air flow | ♦ | Clogged condenser or | ♦ | Clean |
| pressure | through condenser. | radiator fins. | ♦ | Check voltage and fan rpm | |
| abnormally high | ♦ | Condenser or radiator | ♦ | Check fan direction | |
| fan not working properly. | |||||
| Discharge (high) | Line to condenser is | Restricted flow of | Restricted lines. | ||
| pressure | excessively hot. | refrigerant in system. | |||
| abnormally high | |||||
| Discharge pressure | Excessive bubbles in sight | Insufficient refrigerant in | ♦ | Check for leak. | |
| abnormally low. | glass; condenser is not hot. | system. | ♦ | Charge system. | |
| Discharge pressure | High or low pressures are | ♦ Faulty compressor | Replace the compressor. | ||
| abnormally low. | balanced soon after | discharge valve. | |||
| stopping compressor. Low | ♦ | Faulty compressor seal. | |||
| side is higher than normal. | |||||
| Discharge pressure | Outlet of expansion valve is | ♦ | Faulty expansion valve. | ♦ | Replace. |
| abnormally low. | not frosted, and low | ♦ | Moisture in system. | ♦ | Discharge, evacuate and recharge |
| pressure line is not cold. | with specified amount. | ||||
| Low pressure gauge | |||||
| indicates vacuum. | |||||
| Suction (low) | Excessive bubbles in sight | Insufficient refrigerant in | ♦ | Repair the leaks. | |
| pressure | glass; condenser is not hot. | system. | ♦ | Discharge, evacuate and recharge | |
| abnormally low. | with specified amount. | ||||
| ♦ | Charge as required. | ||||
| Suction (low) | Expansion valve is not | ♦ | Frozen expansion valve | ♦ | Discharge, evacuate and recharge |
| pressure | frosted, and low pressure | (moisture in system) | with specified amount. | ||
| abnormally low. | line is not cold. Low | ♦ | Faulty expansion valve | ♦ | Replace the expansion valve. |
| pressure gauge indicates | |||||
| vacuum. | |||||
| Suction (low) | Discharge temperature is | Frozen evaporator | Run the fan with compressor off, then | ||
| pressure | low and the air flow from | check evaporator temperature sensor. | |||
| abnormally low. | vents is restricted. | ||||
| Suction (low) | Expansion valve is frosted. | Clogged expansion valve | Clean or replace. | ||
| pressure | |||||
| abnormally low. | |||||
| Suction (low) | Receiver/dryer outlet is | Clogged receiver/dryer | Replace | ||
| pressure | cool, and inlet is warm | ||||
| abnormally low. | (should be warm during | ||||
| operation). | |||||
| Suction pressure | Low pressure hose and | ♦ | Expansion valve open | Repair or replace. | |
| abnormally high. | check joint are cooler than | too long. | |||
| the temperature around | ♦ | Loose expansion | |||
| evaporator | capillary tube. | ||||
| Suction pressure | Suction pressure is lowered | Excessive refrigerant in | Discharge, evacuate and recharge with | ||
| abnormally high. | when condenser is cooled | system. | specified amount. | ||
| by water. | |||||
| Suction pressure | High and low pressure are | ♦ | Faulty gasket. | Replace the compressor. | |
| abnormally high. | equalised as soon as the | ♦ | Faulty high pressure | ||
| compressor is stopped, and | valve. | ||||
| both gauges fluctuate while | ♦ | Foreign particle stuck in | |||
| running. | high pressure valve. | ||||
| Suction and | Reduced air flow through | ♦ | Clogged condenser or | ♦ | Clean |
| discharge | condenser | radiator fins. | ♦ | Check voltage and fan rpm | |
| pressures | ♦ | Condenser or radiator | ♦ | Check fan direction | |
| abnormally high | fan not working properly. | ||||
| Suction and | No bubbles in sight glass | Excessive refrigerant in | Discharge, evacuate and recharge with | ||
| discharge | when condenser is cooled | system | specified amount | ||
| pressures | by water | ||||
| abnormally high | |||||
| Suction and | Low pressure hose and | Clogged or kinked low | Repair or replace | ||
| discharge | metal end areas are cooler | pressure hose parts | |||
| pressures | than evaporator | ||||
| abnormally low | |||||
| Suction and | Temperature around | Clogged high pressure line | Repair or replace | ||
| discharge | expansion valve is too low | ||||
| pressures | compared with that around | ||||
| abnormally low | receiver/dryer | ||||
| Refrigerant leaks | Compressor clutch is dirty | Compressor high pressure | Replace the compressor | ||
| line | |||||
| Refrigerant leaks | Compressor bolt(s) dirty | Leaking around bolt(s) | Tighten bolt(s) or replace compressor | ||
| Refrigerant leaks | Compressor gasket is wet | Gasket leaking | Replace the compressor | ||
| with oil | |||||