PDF p. 1078 · 22-23
Connect battery power to the No. 3 terminal, ground the No. 2 terminal and connect a test light between the No. 1 and No. 3 terminals.
NOTE: Use a 12V, 3 W - 18 W test lights.
Dip the A/C thermostat into a cup filled with ice water and check the test light.
The light should go off at 4 - 6°C (39 - 43°F) or less and should come on at 5 - 7°C (41 - 45°F) or more.
If the light doesn’t come on and go off as specified, replace the thermostat.

Relays
Test
There should be continuity between the No. 1 and No. 2 terminals when power and ground are connected t the No. 3 and No. 4 terminals and there should be no continuity when power is disconnected.

- Radiator fan relay
- Condenser fan relay
- Compressor clutch relay